Common Questions
What maintenance does a Process Chiller need?+
A maintenance visit checks the Condenser and its Fans, refrigerant pressures, superheat and subcooling, and the Compressors, Contactors and electrical connections. On the fluid side, we check glycol or water concentration and condition, flow, Pumps, Strainers and filters, and test the safety switches, flow switch, sensors and alarms.
How often should a Process Chiller be serviced?+
It depends on the equipment and how hard it runs. Most Process Chillers need 2 to 4 visits a year, and we set the schedule in your Maintenance & Service Agreement.
Why is our Process Chiller not cooling?+
Start with the alarm on the Chiller display. Common causes are low flow (a failed Pump, clogged Strainer or filter, air in the loop or a closed Valve), high-pressure trips from a dirty Condenser or failed Condenser Fan, low-pressure trips from a refrigerant leak, or a failed Compressor, Contactor or Relay. A process load that has grown past the Chiller’s capacity can also cause it.
Why won’t our Process Chiller start?+
Check for a tripped breaker or disconnect and any alarm on the display. Common causes are a safety lockout from high or low pressure, a flow switch that sees no flow, a phase monitor fault, a failed control power Transformer or Contactor, or a remote start signal that is not enabled.
How do you size a Process Chiller?+
We size it from your cooling load, temperatures and flow, and confirm it during the quote.
Can we rent a Chiller during a breakdown?+
Yes. We rent Air-Cooled Glycol Chillers, Portable Glycol Chiller / Heaters and Portable Glycol Unit Coolers for planned work and breakdowns, and we deliver and hook them up. Request a rental and we’ll confirm size, power and connections for your site.