Walk-In Cooler Not Cooling? Common Causes
The usual causes when a Walk-In Cooler will not hold temperature are a Condenser that cannot reject heat, an Evaporator Coil covered in ice, warm air getting in around the door, a refrigerant leak, or a failed Fan, Compressor or control part. Check the simple things below first, and move product to another cold space if the box keeps warming.
Serving Sonoma and Napa counties
1. A dirty or blocked Condenser
The Condensing Unit, often on the roof or an outside wall, has to push heat out. Dust, grease, leaves and debris on the Condenser Coil, or a failed Condenser Fan, make the system run longer and lose capacity, especially on hot days.
2. Ice on the Evaporator Coil
If the coil inside the box is covered in ice, air cannot pass through it. It is usually a defrost problem: a failed defrost heater, timer or termination switch, or a drain line that froze and backed up.
3. Door, gasket and heater problems
A door that does not close on its own, a torn gasket, a failed door heater or a missing strip curtain lets warm, moist air in. That adds load and builds ice on the coil.
4. A refrigerant leak
A slow leak lowers the charge, so the system runs constantly and never quite reaches setpoint. A technician finds it by reading pressures, superheat and subcooling, then leak checking the system.
5. A failed part
A failed Evaporator Fan Motor, Contactor, Capacitor, thermostat or Expansion Valve can each stop cooling. Check these before suspecting the Compressor.
What to check before you call
Note the box temperature and how long it has been warm, whether the Evaporator Fans are running, whether the coil is iced, and whether the Condensing Unit outside is running. Make sure the door closes and seals, and keep it closed as much as you can.