Refrigerant Leak Inspections in California
California’s Refrigerant Management Program (RMP), run by the California Air Resources Board (CARB), covers any stationary Refrigeration system holding more than 50 pounds of high-GWP refrigerant. How often you inspect depends on how many pounds the largest system holds, not on its tons of cooling. We do these inspections and give you the report for your files.
Serving Sonoma and Napa counties

| Refrigerant in the system | RMP size | Leak inspections | Registration |
|---|---|---|---|
| 50 lb or less | Not covered | None required (normal service practices still apply) | None |
| Over 50 to under 200 lb | Small | At least once a year (every 365 days) | Register, no fee, no annual report |
| 200 to under 2,000 lb | Medium | At least 4 times a year (every 90 days) | Register, $170 fee, annual report |
| 2,000 lb or more | Large | Every 90 days for parts outside a building; parts enclosed in a building need an automatic leak detection system, calibrated every year | Register, $370 fee, annual report |
Pounds, not tons
The RMP counts the full refrigerant charge of each system in pounds. A Chiller’s cooling tons do not decide it. The nameplate or the service records usually list the charge; if not, we can work it out for you.
Automatic leak detection
Small and Medium systems watched by an automatic leak detection system that meets the rule do not need the periodic inspections. Large systems with parts inside a building must have one.
Leaks have to be fixed within 14 days
A leak found during an inspection, or at any other time, must be repaired within 14 days and checked again after the repair. A system also gets a leak check before refrigerant is added. If a repair cannot be done in time, the rule has its own steps, and repeated failures can require a plan to retrofit or retire the system.
Records
Keep service records for each system on site for at least 5 years: inspections, repairs and refrigerant added. Our report covers each of these.
Air conditioning
Stationary air conditioning systems are not registered under the RMP. Winery glycol Chillers, cold storage and food plant Refrigeration usually are, when they hold more than 50 pounds.
Combining with maintenance
For Maintenance & Service Agreement customers, leak inspections are scheduled with regular maintenance visits, so they are not missed. Rules as of November 2026; CARB’s Refrigerant Management Program pages have the full text.