Refrigerant Leak Inspections in California

California’s Refrigerant Management Program (RMP), run by the California Air Resources Board (CARB), covers any stationary Refrigeration system holding more than 50 pounds of high-GWP refrigerant. How often you inspect depends on how many pounds the largest system holds, not on its tons of cooling. We do these inspections and give you the report for your files.

Serving Sonoma and Napa counties

Air-cooled Chiller beside Boilers, Pumps and insulated Piping
Leak inspection schedule by system size (CARB RMP, section 95385)
Refrigerant in the systemRMP sizeLeak inspectionsRegistration
50 lb or lessNot coveredNone required (normal service practices still apply)None
Over 50 to under 200 lbSmallAt least once a year (every 365 days)Register, no fee, no annual report
200 to under 2,000 lbMediumAt least 4 times a year (every 90 days)Register, $170 fee, annual report
2,000 lb or moreLargeEvery 90 days for parts outside a building; parts enclosed in a building need an automatic leak detection system, calibrated every yearRegister, $370 fee, annual report

Pounds, not tons

The RMP counts the full refrigerant charge of each system in pounds. A Chiller’s cooling tons do not decide it. The nameplate or the service records usually list the charge; if not, we can work it out for you.

Automatic leak detection

Small and Medium systems watched by an automatic leak detection system that meets the rule do not need the periodic inspections. Large systems with parts inside a building must have one.

Leaks have to be fixed within 14 days

A leak found during an inspection, or at any other time, must be repaired within 14 days and checked again after the repair. A system also gets a leak check before refrigerant is added. If a repair cannot be done in time, the rule has its own steps, and repeated failures can require a plan to retrofit or retire the system.

Records

Keep service records for each system on site for at least 5 years: inspections, repairs and refrigerant added. Our report covers each of these.

Air conditioning

Stationary air conditioning systems are not registered under the RMP. Winery glycol Chillers, cold storage and food plant Refrigeration usually are, when they hold more than 50 pounds.

Combining with maintenance

For Maintenance & Service Agreement customers, leak inspections are scheduled with regular maintenance visits, so they are not missed. Rules as of November 2026; CARB’s Refrigerant Management Program pages have the full text.

Updated November 16, 2026

Request a Service or Quote

We’ll follow up to confirm the details and schedule a visit.

Equipment down or production affected?

After-hours service is for Maintenance & Service Agreement customers. Online requests are reviewed during office hours.

(707) 544-1277

Prefer to write a message or attach a file? Use our contact form.