Glycol Chiller Not Cooling? Common Causes

A Glycol Chiller that runs but does not cool usually has one of five problems: low glycol flow, a Condenser that cannot reject heat, a refrigerant problem, a glycol mix that is too weak, or more load than the Chiller can carry. Start with the alarm on the display, then work through the list below.

Serving Sonoma and Napa counties

Air-cooled Chiller with glycol Pumps and insulated supply and return Piping

1. Low glycol flow

If glycol is not moving, the Tanks do not get cold no matter how hard the Chiller runs. Look for a failed or air-locked Pump, a clogged Strainer, a closed or stuck Valve, or a low glycol level in the reservoir. Low flow is also the most common cause of freeze-ups, because the glycol sits too long in the Evaporator.

2. A dirty Condenser or failed Condenser Fan

An air-cooled Chiller has to push heat out through its Condenser Coil. Dust, leaves, cottonwood and grape debris block the coil, and a failed Fan or Motor stops the airflow. The Chiller then trips on high pressure or runs with reduced capacity, worst on hot afternoons.

3. A refrigerant problem

A leak lowers the refrigerant charge, and the Chiller trips on low pressure or loses capacity. A failing Expansion Valve or Solenoid Valve can starve the Evaporator in the same way. These need a technician with gauges to read pressures, superheat and subcooling.

4. A weak or wrong glycol mix

Glycol that has been diluted over time, topped off with water, or mixed for a warmer setpoint can freeze inside the Evaporator or Heat Exchanger. The mix must protect well below your lowest setpoint. Check the concentration with a refractometer.

5. More load than the Chiller can carry

During crush, many Tanks can call for cooling at once. A Chiller that keeps up the rest of the year can fall behind. If everything else checks out, the answer may be added capacity: a larger Chiller, a second Chiller in parallel, or a rental for harvest.

What to check before you call

Write down the alarm or code on the display, the glycol supply and return temperatures, whether the Pumps are running and which Tanks are affected. Check the breaker and that nothing is blocking the Condenser. A photo of the Chiller nameplate helps us bring the right parts.